BK Gulf FM
Provide complete turnkey Facilities
Management Service i.e. MEP Maintenance, Condition Surveys, All types of Cleaning
(Office, Façade, General Cleaning etc.), Provision of |
 |
|
Security Personnel and Surveillance
systems and maintenance and subcontractor management from pre-qualification stage through
to Operations.
BK Gulf FM conducts PAT/FAT testing on a regular and scheduled
basis, when was the last time you had your Portable appliances checked for safety
reasons?
BK
Gulf FM has their own Fire Systems & Maintenance division
(BCL Fire) – who are
fully licensed by Civil Defense to carry out related maintenance works.
|
|
- Inspect Control Unit condition and clean.
- Check indications and change bulbs as necessary.
- Simulate fire, fault conditions & check operation.
- Check charger output, adjust as necessary.
- Check battery condition and clean.
- Inspect System components and cabling, joints and terminations (where visible).
- Test all detectors on each zone and check for correct operation.
- If site conditions permit, check sounder circuit output and general audibility.
Check audibility of one sounder in rotation.
- Remove all detectors and clean. Recalibrate where applicable. Replace and test.
- Check all break glasses. Replace if necessary. Check operation.
HOSEREELS
- Visual inspection of system all joints and fittings (where accessible) for leakage.
Check corrosion levels and paintwork.
- If site conditions permit, exercise isolating valve and auto valve (if fitted) and
flush out Hose. Drain and rewind. Check for unit leakage. All Hose Units to be serviced
each visit.
- Check Hose guides and rollers.
- Clean and check hosereel cabinets. Lubricate the hinges.
- Inspect the swing mechanism of each hosereel unit and lubricate where necessary.
Run out hose, check for damage or deterioration. Check nozzle mechanism.
FIRE PUMP
|
- Visual inspection of Pump Room pipe work, joints and fittings for leakage. Check
corrosion levels and paintwork
- Exercise Electric Pump, check start sequence, check Star/Delta functions.
- Exercise Diesel Pump, check start sequence, oil pressure and temperature (where
fitted), engine speed (where fitted), shutdown mechanism. Check batter(s) and charger.
Check fuel level.
- Annually change oil and filters, controller fuses, check pump alignment and coupling
condition.
- Check pump motor set, mountings, bearings and leakage.
- Check pressure switch operation, settings, flow switches, pump run timers, system
standing pressure and fall-back.
- Check and exercise all valves.
- Check condition of tank, water levels and level switches (if fitted).
- Lubricate moving parts as necessary.
- Check weight.
- Inspect Pressure Gauge (if fitted.)
- support brackets.
DRY RISER / WET RISER
- Check and exercise landing Valves (where possible).
- Check Breaching Inlet and Drain Valve.
- Inspect condition of Hoses (if fitted).
- Lubricate moving parts.
- Annually pressure test the pipes.
FOAM SYSTEM
- Clean and check condition of valves.
- Check operation of valves.
- Check pump operations.
- Check Linear Heat Sensor operation.
- Check condition of nozzles, pipe work & supports, repair or replace where necessary.
- Check Sounder / Flash lamps.
- Check control panel operation.
- Check Battery condition.
- If site conditions allow check the flow with water only.
- After flow test drain out and clean all Nozzle pipelines.
- Foam circulation.
- Sampling and testing of foam.
- Top up of foam – (free supply from client.)
CARBON DIOXIDE SYSTEM
- Clean and check all Heat Detectors.
- Clean and check Sirens.
- Clean, check Lamp and Manual Release units.
- Check Cylinder Valves / Selection Valves.
- Check Alarm panel. Release Control Panel Operations.
- Check Shutter Door release mechanism.
- Check all power Supply units and batteries.
- Check Repeat Signal to main Fire Alarm Control Panel.
EMERGENCY LIGHTS
- Clean and check for the proper functioning of each emergency light (and programme
if necessary).
- Check the battery(s) and battery chargers.
- Replace bulbs / tubes if found defective.
FIRE DOORS
- Check for proper functioning of fire doors.
- Lubricate hinges of fire doors.
Monthly Inspection
- Check fire alarm panel condition and test few signals.
- Check battery condition and charging levels.
- Visually inspect complete system, confirm all in normal condition.
- Check fire pump condition and test.
- Check fuel and oil levels in diesel engine.
- Check all fire extinguishers.
<<Back to FM
|
|