BK Gulf Facilities Management

BK Gulf FM
Provide complete turnkey Facilities Management Service i.e. MEP Maintenance, Condition Surveys, All types of Cleaning (Office, Façade, General Cleaning etc.), Provision of
Security Personnel and Surveillance systems and maintenance and subcontractor management from pre-qualification stage through to Operations.

BK Gulf FM conducts PAT/FAT testing on a regular and scheduled basis, when was the last time you had your Portable appliances checked for safety reasons?      

BK Gulf FM has their own Fire Systems & Maintenance division
(BCL Fire) – who are fully licensed by Civil Defense to carry out related maintenance works.

 

 

     

 

  • Inspect Control Unit condition and clean.
  • Check indications and change bulbs as necessary.
  • Simulate fire, fault conditions & check operation.
  • Check charger output, adjust as necessary.
  • Check battery condition and clean.
  • Inspect System components and cabling, joints and terminations (where visible).
  • Test all detectors on each zone and check for correct operation.
  • If site conditions permit, check sounder circuit output and general audibility. Check audibility of one sounder in rotation.
  • Remove all detectors and clean. Recalibrate where applicable. Replace and test.
  • Check all break glasses. Replace if necessary. Check operation.

HOSEREELS

  • Visual inspection of system all joints and fittings (where accessible) for leakage. Check corrosion levels and paintwork.
  • If site conditions permit, exercise isolating valve and auto valve (if fitted) and flush out Hose. Drain and rewind. Check for unit leakage. All Hose Units to be serviced each visit.
  • Check Hose guides and rollers.
  • Clean and check hosereel cabinets. Lubricate the hinges.
  • Inspect the swing mechanism of each hosereel unit and lubricate where necessary. Run out hose, check for damage or deterioration. Check nozzle mechanism.

FIRE PUMP

  • Visual inspection of Pump Room pipe work, joints and fittings for leakage. Check corrosion levels and paintwork
  • Exercise Electric Pump, check start sequence, check Star/Delta functions.
  • Exercise Diesel Pump, check start sequence, oil pressure and temperature (where fitted), engine speed (where fitted), shutdown mechanism. Check batter(s) and charger. Check fuel level.
  • Annually change oil and filters, controller fuses, check pump alignment and coupling condition.
  • Check pump motor set, mountings, bearings and leakage.
  • Check pressure switch operation, settings, flow switches, pump run timers, system standing pressure and fall-back.
  • Check and exercise all valves.
  • Check condition of tank, water levels and level switches (if fitted).
  • Lubricate moving parts as necessary.
  • Check weight.
  • Inspect Pressure Gauge (if fitted.)
  • support brackets.

DRY RISER / WET RISER

  • Check and exercise landing Valves (where possible).
  • Check Breaching Inlet and Drain Valve.
  • Inspect condition of Hoses (if fitted).
  • Lubricate moving parts.
  • Annually pressure test the pipes.

FOAM SYSTEM

  • Clean and check condition of valves.
  • Check operation of valves.
  • Check pump operations.
  • Check Linear Heat Sensor operation.
  • Check condition of nozzles, pipe work & supports, repair or replace where necessary.
  • Check Sounder / Flash lamps.
  • Check control panel operation.
  • Check Battery condition.
  • If site conditions allow check the flow with water only.
  • After flow test drain out and clean all Nozzle pipelines.
  • Foam circulation.
  • Sampling and testing of foam.
  • Top up of foam – (free supply from client.)

CARBON DIOXIDE SYSTEM

  • Clean and check all Heat Detectors.
  • Clean and check Sirens.
  • Clean, check Lamp and Manual Release units.
  • Check Cylinder Valves / Selection Valves.
  • Check Alarm panel. Release Control Panel Operations.
  • Check Shutter Door release mechanism.
  • Check all power Supply units and batteries.
  • Check Repeat Signal to main Fire Alarm Control Panel.

EMERGENCY LIGHTS

  • Clean and check for the proper functioning of each emergency light (and programme if necessary).
  • Check the battery(s) and battery chargers.
  • Replace bulbs / tubes if found defective.

FIRE DOORS

  • Check for proper functioning of fire doors.
  • Lubricate hinges of fire doors.

Monthly Inspection

  • Check fire alarm panel condition and test few signals.
  • Check battery condition and charging levels.
  • Visually inspect complete system, confirm all in normal condition.
  • Check fire pump condition and test.
  • Check fuel and oil levels in diesel engine.
  • Check all fire extinguishers.